TRI PDU PDUMV30HV MeteredPower
OUTPUT
Frequency compatibility
50 / 60 Hz
Output nominal voltage
208/240V Overload protection
Outlets are arranged in two separately breakered load banks. The top 15A breaker covers outlets on the upper half, the bottom 15A breaker covers outlets on the lower half of the PDU. Each breakered bank covers 12 C13 and 3 C19 outlets. Outlet quantity / type
30 total (6 C19, 24 C13) INPUT
Recommended Electrical Service
208V, 240V
Maximum Input Amps (A)
30
Maximum Input Amps (A) Details
Agency de-rated to 24A continuous Input connection type
L6-30P (208/240V 30A)
Plug Type
NEMA L6-30P (30A 208/240V)
Input cord length (ft.)
10 LEDS ALARMS
Front panel LEDs Includes 2 built-in 2-character LED meters to display power consumption of items plugged into each separately breakered 15A loading bank. PHYSICAL
Shipping weight (kg)
5.9
Unit Dimensions (HWD/in)
63.75 x 2.25 x 3.75
Shipping Dimensions (HWD/in)
64.5 x 3.5 x 4.75 Unit weight (kg)
3.6
Material of construction
Aluminum Style
Vertical Rackmount, Wallmount, Raceway, Workbench
Form factors supported
0u vertical installation in equipment racks, plus under-counter and wallmount Certifications
Tested to UL60950-1 (USA, Canada), NOM (Mexico)
WARRANTY
Lifetime
© 2024 BrokerDen. All rights reserved.